Tag Archives: 15 kV switchgear

medium voltage switchgear for power distribution to data center

Building Custom Switchgear for Power Distribution

Custom Switchgear Design for Managing Facility Power

Designing, Building Switchgear for Power Distribution

medium voltage switchgear for power distribution to data center

Electrical power enters a facility through one or two connections, but it’s distributed in multiple directions once it gets inside. If one circuit supplies a transformer, another might go to a production area, and another delivers power to a separate building.

The challenge is organizing power so operators can control individual circuits and perform maintenance without shutting down the entire facility.

That’s the purpose of your custom switchgear. Instead of forcing every facility into the same standard design, your custom equipment is built around how the facility actually receives, distributes and uses electricity.

Electrical gear in projects like this (see video) includes Main-Tie-Main, Main with Feeders and Double Main with Feeders lineups. ABB VersaRupter and Powercon switches in the video below control incoming power and outgoing circuits.

What Does Custom Switchgear Do?

Your switchgear is a central control point between an incoming electrical source and the equipment that uses that power. It gives facility personnel an organized way to connect, disconnect and direct electricity through the distribution system.

A complete lineup can include incoming main sections, tie sections and multiple feeder sections. Each section has a particular job, but all of them are assembled into one coordinated system.

The result is equipment designed to:

  • Receive power from one or more sources
  • Distribute power to several circuits
  • Separate sections for maintenance
  • Adapt to changing operating conditions
  • Prepare for possible future expansion

That’s why custom switchgear manufacturing begins with the customer’s power-distribution needs and not a predetermined equipment configuration.

Need a Custom Switchgear Configuration?

Why One Switchgear Design Doesn’t Fit Every Facility

Buildings and industrial facilities don’t all use power in the same way. A small facility might get power through one incoming source and distribute it to only a few circuits. A larger plant, campus or processing facility can have two sources, multiple transformers and several operating areas.

The physical location also affects the equipment design. Floor space, cable-entry direction, indoor or outdoor installation and access for maintenance all influence the switchgear lineup needed.

Custom switchgear brings requirements together. Your switchgear manufacturer can arrange the mains, ties and feeders to the facility’s power system while considering the available installation space.

Even your equipment enclosure needs to be considered. BCS incorporates custom electrical enclosures for switchgear when environmental conditions, dimensions or equipment layouts need something other than a standard cabinet.

Main with Feeders: One Source, Several Circuits

A Main with Feeders switchgear lineup is the easiest configuration to understand. Power enters through one main switch and travels along the internal bus to several feeder switches.

Each feeder controls an outgoing circuit. Those circuits serve transformers, large equipment, separate buildings or different facilities.

You can think of the main as the entrance to the system and the feeders as the individual exits. Electricity enters at one point and goes to where it’s needed.

The feeder arrangement also gives the facility more control over individual circuits. If one transformer or building needs to be disconnected, its feeder can be isolated without automatically turning off every other circuit supplied by the lineup.

A Main with Feeders meets the need when a facility has one primary source but needs to distribute power to multiple destinations.

15kv switchgear manufacturing

ABB VersaRupter and Powercon switches shown in this video are electrical power switches for controlling parts of the system. Depending on the lineup, a switch may work as a main, tie or feeder.

The main switch controls incoming power. A tie switch connects or separates bus sections. Feeder switches control the outgoing circuits carrying power to downstream equipment.

Some positions use fused switches, and others use non-fusible designs with circuit breakers helping to protect the electrical system. Selection depends on the project’s power-system requirements.

See Medium-voltage load-interrupter switches explains these individual switch types.

Main-Tie-Main: Dividing Power Into Two Sections

Main-Tie-Main switchgear divides the lineup into two bus sections. Each section has its own main, and a tie switch is positioned between.

During normal operation, the two sides may operate separately. The tie provides a controlled way to connect the sections when the power-system design and approved operating procedure allow.

This arrangement gives your facility greater flexibility. One section may be isolated for maintenance while the other is available, or the system might be configured so one source can temporarily support more loads.

The operating sequence depends on the facility’s sources, equipment capacity and controls. Main-Tie-Main doesn’t automatically mean that a facility will have uninterrupted power. It provides an equipment arrangement supporting power transfers and sectionalized operation when the complete electrical system is designed for those functions.

You can learn more about the individual devices used in these lineups should review our guide to 15 kV switch types in medium-voltage switchgear.

Double Main with Feeders: Organizing Two Sources

A Double Main with Feeders switchgear lineup is designed around two incoming main switches and multiple outgoing feeder switches.

This configuration is used when your facility has two utility services, two transformers, a normal source and an alternate source, or another power design needing separate incoming connections.

The two mains create entry points for power. The feeders then distribute that power to the designated loads.

Compared with a Main-Tie-Main arrangement, a Double Main with Feeders lineup doesn’t necessarily have a tie between the two sections. Its design is developed around how the two sources and their connected loads operate.

👉 Point to Remember: custom switchgear manufacturing allows two incoming power paths and several outgoing circuits to be organized into one clearly arranged equipment lineup.

Building Around the Facility Instead of a Catalog

Standard equipment works when your building and power system match the manufacturer’s available arrangements. Existing facilities, replacement projects and expanding power systems don’t always fit standard dimensions or layouts.

A custom manufacturer can consider the entire installation, including:

  • Number of incoming power sources
  • Number of outgoing circuits
  • Location of mains, ties and feeders
  • Indoor or outdoor installation
  • Cable-entry and exit locations
  • Available floor space
  • Access for operation and maintenance
  • Provisions for future expansion

This is important when new equipment connects to existing transformers, cables or electrical infrastructure. The switchgear has to work as part of the facility’s complete power system, not as an isolated piece of equipment.

Talk with BCS about a switchgear lineup built around your facility’s sources, loads, available space and operating needs.

What You Don’t See in the Finished Lineup

Once a switchgear lineup is completed, its appearance can make the project seem straightforward. The sections are aligned, doors are installed, switches are labeled and the equipment is ready for shipment.

What you don’t immediately see is the work required to reach that point.

Before manufacturing begins, the switchgear build team understands your system including how the equipment should be arranged. Enclosures are fabricated, switching devices installed, busses assembled and control wiring completed. Components are positioned so the equipment can be installed, operated and maintained.

This planning and craftsmanship are what turn individual switches, conductors and metal compartments into a coordinated power-distribution system.

Testing the Complete Switchgear Lineup

Testing is another important part of custom manufacturing. Finished equipment is inspected to confirm that its components, wiring, switch operation and mechanical features match the intended design.

Testing identifies issues before the lineup reaches the jobsite, where corrections can be difficult and disruptive. Testing gives you confidence the assembled sections operate together as intended.

BCS provides switchgear testing services for electrical equipment used in demanding commercial and industrial power systems.

Choosing the Right Configuration

The correct arrangement starts with understanding how the facility receives and distributes power.

Main with Feeders: configuration supports one incoming source and several outgoing circuits. Main-Tie-Main: divides power into two sections and adds a tie for greater operating flexibility. Double Main with Feeders: organizes two incoming sources and multiple outgoing circuits.

No single arrangement is right for every project. The best solution is the one designed around your facility’s sources, loads, operating plans, available space and long-term needs.

That’s the real value of custom switchgear. You get an organized system for managing facility power today, providing flexibility to support how your power system needs to operate for years to come.

15kv switchgear manufacturing

15 kV Switch Types, Applications in Medium-Voltage Switchgear

15 kV Switch Types in Medium-Voltage Switchgear

15kv switchgear manufacturing

Medium-Voltage Load-Interrupter Switches

Think of a medium-voltage load-interrupter switch as a heavy-duty shutoff valve on a city water main. The valve controls normal flow and lets workers to isolate part of the system. In the same way, a switch connects, disconnects or isolates the normal flow of medium-voltage electricity.

An arc forms when energized contacts separate. The switch uses an arc-control system and quick-make, quick-break mechanism to interrupt its rated load current. Stored-energy mechanisms make the switching action fast and consistent.

A load-interrupter switch isn’t designed to clear high-level fault current by itself. That’s done by properly rated power fuses or a relay-controlled circuit breaker.

15 kV switches for medium voltage power distribution systems control power, isolate equipment into manageable parts.

15kV_switch_diagram

Understanding the 15 kV Switchgear Equipment Class

The term 15 kV switchgear describes an equipment class, not necessarily a system operating at exactly 15,000 volts. This equipment is applied on nominal systems such as 4.16 kV, 12.47 kV and 13.8 kV.

Voltage is only one part of the specification. You’ll also need to consider continuous current, load-interrupting current, fault-closing capability, maximum fault current and basic impulse level, or BIL. BIL indicates the ability of the equipment’s insulation system to withstand short-duration voltage surges.

Equipment ratings need to match system voltage, available fault current, grounding method, connected load and intended operating sequence. These requirements should be set through system studies and an accurate one-line diagram.

Need Help?

15 kV Fused Switches and Fault Protection

A 15 kV fused switch combines a load-interrupter switch with medium-voltage fuses. The switch controls normal power flow and isolates the circuit, while the fuses protect against overcurrents and short circuits.

It’s a simpler alternative to using a circuit breaker with protective relays and instrument transformers. The fuses need to be properly sized for the transformer’s normal current, startup inrush, overload limits and available fault current. An undersized fuse might open when the transformer starts, while an oversized fuse might not provide enough protection.

Medium-Voltage Disconnect and Isolation Switches

A medium-voltage disconnect switch provides an isolation point between an electrical source and the equipment being serviced. Visible-open construction lets personnel confirm the physical switch position as part of an established safety procedure.

You shouldn’t assume every disconnect can interrupt current. A load-break disconnect can open its rated load current. A non-load-break disconnect must only be operated after another device has removed the load.

Safety note: visible isolation doesn’t replace lockout/tagout, absence-of-voltage testing, protective grounding or other required electrical-safety practices.

Main and Tie Switches in Metal-Enclosed Switchgear

In 15 kV metal-enclosed switchgear, the main switch controls power to the lineup from a utility, generator or upstream. The main may be fused or unfused, depending on where fault protection is.

A tie switch connects or separates two bus sections. In main-tie-main switchgear, two main switches normally supply separate sections while the tie remains open. If one source becomes unavailable, an approved transfer sequence lets the other source serve both sections.

Medium-Voltage Feeder Switches

A medium-voltage feeder switch controls an outgoing circuit supplying a transformer, motor, separate building or another switchgear lineup. Multiple feeders let you isolate one circuit without de-energizing every load connected to the bus.

Feeder switches may be fused or protected elsewhere in the system. Selection should consider the connected load, cable characteristics, switching duty, available fault current and coordination with upstream and downstream devices.

Transformer-Primary Switch Applications

A transformer-primary switch is installed on the medium-voltage side of a transformer. It allows you to energize, de-energize and isolate that transformer without opening the entire upstream system.

Fused load-interrupter switches are widely used in this position. The switch performs normal transformer switching and isolation, while the fuses respond to qualifying overcurrent and short-circuit conditions.

Coordination between the primary fuses and secondary main breaker is important. When system conditions permit, a downstream breaker should clear a secondary fault before the primary fuse operates.

Fused Switch Versus a 15 kV Circuit Breaker

A fused switch is practical when you need load switching, isolation and straightforward fault protection. A 15 kV circuit breaker, however, can interrupt both normal current and fault current within its ratings.

Protective relays monitor current, voltage and other electrical conditions, then command the breaker to trip when they identify a qualifying fault. Circuit breakers can provide adjustable protection, frequent switching, remote operation, event recording, communications or advanced transformer, generator and bus protection.

Your decision shouldn’t be based on initial price. Consider switching frequency, coordination requirements, maintenance resources, automation needs and outage consequences.

Specifying Engineered 15 kV Switchgear

When specifying engineered 15 kV switchgear, begin with an one-line diagram. Define the nominal voltage, grounding method, continuous load, available fault current and equipment served by every feeder.

Identify the required main, tie and feeder arrangement; fused or unfused positions; manual or motor operation; interlocking; metering; control power; communications; cable-entry direction and future expansion provisions.

Indoor and outdoor installations can have different enclosure, heating and environmental requirements. Cable-bending space, access to fuses and terminations, and compartment arrangement affect installation and long-term maintainability.

BCS Switchgear can coordinate main, tie, feeder and transformer-primary sections for permanent or temporary power applications. By treating the lineup as part of the complete distribution system, you’ll receive equipment designed around your loads, installation requirements and operating sequence.

Term Definition
15 kV class An equipment voltage and insulation class commonly applied to systems such as 4.16 kV, 12.47 kV and 13.8 kV.
BIL Basic impulse level, indicating the insulation’s ability to withstand short-duration voltage surges.
Continuous-current rating The amount of current equipment can carry continuously under its specified operating conditions.
Fault-closing rating The switch’s ability to close safely onto a circuit carrying a specified level of fault current.
Feeder switch A switch that controls an outgoing medium-voltage circuit supplying a transformer, motor, building or other equipment.
Interlock A mechanical, electrical or key-based device that helps prevent an unsafe operating sequence.
Load-interrupter switch A switch designed to open and close a circuit carrying normal load current within its specified rating.
Main switch The switch that controls incoming power to a bus or medium-voltage switchgear lineup.
Power fuse A medium-voltage fuse designed to interrupt qualifying overcurrent or short-circuit current.
Tie switch A switch used to connect or separate two bus sections for load transfer, sectionalizing or maintenance flexibility.
Transformer-primary switch A switch installed on the medium-voltage side of a transformer to provide switching and circuit isolation.

15kV Switch for Power Distribution FAQ

What does 15 kV class mean?
The term 15 kV class describes the equipment’s voltage and insulation class. It doesn’t mean the electrical system must operate at exactly 15,000 volts. Properly rated 15 kV equipment is commonly used on 4.16 kV, 12.47 kV and 13.8 kV systems.
What does a 15 kV load-interrupter switch do?
A 15 kV load-interrupter switch opens and closes a medium-voltage circuit carrying normal load current. It also provides an isolation point for inspection and maintenance when used according to the equipment manufacturer’s instructions and required safety procedures.
Can a 15 kV load-interrupter switch clear a short circuit?
A load-interrupter switch is generally designed to interrupt normal load current, not high-level fault current by itself. Medium-voltage power fuses or a properly rated circuit breaker typically clear short circuits and other qualifying faults.
What is the difference between a fused switch and an unfused switch?
An unfused switch provides switching and isolation, while fault protection is supplied elsewhere in the electrical system. A fused switch combines a load-interrupter switch with medium-voltage power fuses that provide overcurrent and short-circuit protection.
Why are fused switches used on transformer primaries?
A fused transformer-primary switch provides normal switching, circuit isolation and fault protection in one practical arrangement. The switch controls power to the transformer, while the fuses respond to qualifying overcurrents and short circuits.
What does a tie switch do in 15 kV switchgear?
A tie switch connects or separates two medium-voltage bus sections. In a main-tie-main system, it can support load transfer and maintenance flexibility when the sources, transformers, bus and switches have adequate capacity and the proper interlocks are installed.
When should a circuit breaker be used instead of a fused switch?
A medium-voltage circuit breaker may be preferable when you need adjustable protection, frequent switching, remote operation, automated control, event recording or more advanced system coordination. Protective relays monitor electrical conditions and command the breaker to trip when a qualifying fault occurs.
Can 15 kV switches be operated remotely?
Yes. Motor-operated 15 kV switches can support remote switching, automatic transfer arrangements and integration with facility control systems. The operating sequence and interlocks must be engineered for the specific application.