Vacuum Circuit Breakers

Switchgear Services to Repair , Upgrade, Replace, Test

Vacuum Circuit Breaker repair, test, replace
Need Help?
888.599.0486

Vacuum Breaker Maintenance and Repair Services

When it’s time for an upgrade or replacing Vacuum Circuit Breakers, Modernization Solutions help you learn about and maintain your vacuum breakers, upgrading active components matching current technologies. Key services include:

✔ Visual inspection for broken parts
✔ Clean, lubricate mechanical linkages
✔ Inspect breakers, remove covers and shields
✔ Inspect for damage, wear and deterioration

Upgrade Vacuum Circuit Breakers

When it’s time to upgrade or replace vacuum circuit breakers, Our Modernization Solutions sustain your existing gear by upgrading components matching current technologies.

BCS Switchgear tests equipment ensuring your gear meets manufacturer, PEARL, NETA and other industry standards.We calibrate equipment for accurate reading.

Replacement Parts for Vacuum Breakers

We know when needing a part for a vacuum circuit breaker, you need the right part and you need it now. Most parts can be shipped in the same day from our stock.

We buy and sell vacuum circuit breakers. Our experience allows us to confidently buy large lots resulting from plant closures and auctions. New and surplus in factory condition.

 

Steps for Servicing a Vacuum Circuit Breaker

  1. Visual Inspection

    • Check insulators, pole unit support, control circuit parts, wiring, and terminals for dirt and cracks.
    • Inspect hardware and operating mechanisms for tightness and proper condition.
  2. Vacuum Interrupter Integrity Test

    • Perform a high potential (hipot) test to check insulation integrity.
    • Assess dielectric strength and identify any defective interrupters.
  3. Mechanism Check

    • Inspect for loose parts, perform measurements, and conduct functional and operational tests.
    • Check contact erosion indicators and motor functionality.
  4. Insulation Maintenance

    • Clean insulation surfaces with a lint-free cloth or mild solvent.
    • Ensure surfaces are dry before reassembly.
  5. Lubrication

    • Apply light machine oil annually or as needed.
    • Operate the breaker manually and electrically to distribute oil.
  6. Troubleshooting

    • Address closing problems by checking alignment and replacing faulty parts.
    • Resolve tripping issues by replacing non-functional components.
  7. Isolation and Cleaning

    • Turn off and isolate the VCB before maintenance.
    • Clean with electrical contact cleaner and re-grease with similar type grease.
  8. Contact Inspection

    • Examine fixed and floating contacts for condition and proper positioning.
  9. Hardware Check

    • Ensure all external parts and hardware are properly fixed.
  10. Functional Testing

    • Use the push button to verify breaker tripping.
  11. Electrical Testing

    • Measure current between phases and between phase and earth in both closed and open states.
 
 